| Hubbell Wiring Device-Kellems Product
Specifications |
| Product Type |
Watertight Insulgrip |
| Body Style |
Straight |
| Material |
Insulated Metallic |
| Service |
Standard |
| Grounding Style |
II |
| Type of Device |
Connector |
| Amperage |
200 |
| Voltage |
250DC/600AC |
| Poles and Wires |
2 Pole, 3 Wire Grounding |
| Color |
|
| Configuration |
UL 1686 C1, Watertight |
| Cord Grip Range |
1.00" - 2.50" (25.0-63.0)
|
| Housing Material |
Aluminum |
| Contact Carrier
Material |
Thermoset Polyester |
| Retainer Material |
Thermoset Polyester |
| Ground, Phase Pins
Material |
Brass. |
| Terminal Screw Material |
Stainless Steel (300 Series).
|
| Assembly Screw Material |
Stainless Steel (300 Series).
|
| Gaskets Material |
Solid Neoprene. |
| Gland Material |
Solid Neoprene. |
| Cover Arm Material |
Epoxy Painted Aluminum |
| Arm Spring Material |
Stainless Steel 300 Series
|
| Cover Material |
Epoxy Painted Aluminum |
| Sealing Gasket Material |
Neoprene. |
| Cord Clamp Material |
Rynite SST35 |
| Clamp Nut Material |
Nickel-Plated Brass |
| Gland Cap Material |
Rynite SST35 |
| Gland Clamp Screws
Material |
Stainless Steel (300 Series)
|
| Cord Clamp Screws
Material |
Stainless Steel (300 Series)
|
| Dielectric Withstand
Voltage |
3000V AC |
| Current Interrupting |
Certified for current
interrupting at full rated current. |
| Temperature Rise |
Max. 30°C temperature rise at
full rated current after 50 cycles of overload at 150% of rated
current. |
| Endurance |
1,000 connect and disconnect
cycles at full current and voltage |
| Impact Resistance |
Per CSA C22.2, No. 182.1,
Paragraph 7.4.2 UL 1682 Section 34 |
| Cord Grip Cable
Retention |
Per CSA C22.2 No. 182.1,
Paragraph 7.3.1 to 7.3.4., UL 1682 Section 33 |
| Cord Accommodation |
Round portable service cords of
diameters commensurate with the device rating as defined in UL
Standard 62, CSA C22.2 No. 49 and the harmonized European
Standards. |
| Terminal Identification |
Terminals identified in
accordance with UL 1682 (1, 2, 3, Green) |
| Product Identification |
Identification and ratings are
a permanently fastened to the device housing |
| Moisture Resistance |
Type 3, 4, 4X per UL 50 and CSA
22.2, No. 94 |
| Flammability |
V0 per UL 94 or CSA C22.2 No.
0.6 |
| Operating Temperatures |
Maximum Continuous 75 deg C
Minimum -40 deg C w/o impact, -25 deg C w/ impact.
|